2.11 SEALED SYSTEM REQUIREMENTS
Refer to Fig. 4.
1. The installation must comply with the requirements of BS6798 and BS5449. Maximum water temperature is 82°C ±
3°C.
2. A safety valve set to operate at 3 bar and a pressure gauge covering the range 0 to 6 bar are incorporated within the
boiler.
3. A 10 litre expansion vessel to BS4841 is fitted and pre-charged to 0.5 bar. This is suitable for a system with a
maximum water content of 140 litres.
4. Water lost from the system shall be replaced from a make-up vessel, and double check valve, mounted higher than the
top of the system and connected as shown in Fig. 4a or manually by a temporary hose connection as shown in Fig. 4b
(remove the temporary hose after use).
Note: Stop valves must comply with the requirements of BS1010:2.
5. The hot water cylinder shall either be the indirect coil type or a cylinder fitted with an immersion calorifier.
6. An automatic air vent should be fitted at the highest point in the system.
2.12 SYSTEM SCHEMATIC
Refer to Fig. 5.
Fig. 5